Direct Drive Gas-Fired Heated Make Up Air Unit - 2000 CFM

SKU:VD-V1D-DFHMU-2000

Direct Drive Gas-Fired Heater, ETL Listed, for use in tempering make-up air. 2000 CFM

Free shipping in continental US
We ship to Canada! Contact us

Direct Gas Fired Heated Make Up Air Unit with 15" Direct Drive Fan

  • Supply Fan handles 2000 CFM @ 0.451" wc ESP, Fan runs at 2020 RPM.
  • Heater supplies 117517 BTUs. 55°F Temperature Rise. [Fuel: Natural Gas]
  • Supply Motor: 2.000 HP, 3 Phase, 208 V, 60Hz, 6.1 FLA, ODP, Premium (E-Plus3) Eff.
  • Down Discharge - Air Flow Right -> Left

200/240 V, Single or Three Phase Input *available, please call for 1 phase input

Construction Features:

  • Sloped Filtered Intake for Size #1 Modular Heater. 21.813" Wide x 44.375" Long x 23.375" High.
  • Includes 3 MV EZ Kleen Metal Mesh Filter. 16"x 20"x 2"
  • RTC Solutions • 40-90°F Discharge Temp Control
  • Gas Manifold for DF1 GM - BTU 0 - 550001 - 7 in. w.c. - 14 in. w.c., No Insurance Requirement (ANSI), BV250-66
  • Motorized Back Draft Damper 16" X 18" for Size 1 Standard & Modular Heater Units w/Extended Shaft, Standard Galvanized Construction, 3/4" Rear Flange, Low Leakage, TFB120S Actuator Included
  • Low Fire Start. Allows the burner circuit to energize when the modulation control is in a low fire position.
  • Gas Pressure Gauge, 0-35", 2.5" Diameter, 1/4" Thread Size
  • Gas Pressure Gauge, -5 to +15 Inches Wc., 2.5" Diameter, 1/4" Thread Size
  • Curb CRB21X71X20INS Insulated On Fan # 1 Flat Curb
  • VAV (Variable-Air-Volume) Wiring Package for Commercial Fans. Manual Speed Control Variable Frequency Drive Included
  • Supply Variable Frequency Drive - 2 HP Max., 200/240 V, Single or Three Phase Input, 7.0 A Max., NEMA 1 Enclosure
  • VFD factory mounted and wired on unit control panel.



Direct Drive Gas-Fired Heated Make Up Air Unit - 2000 CFM