Direct Drive Gas-Fired Heated Make Up Air Unit - 1500 CFM

SKU:VD-V1D-DFHMU-1500

Direct Drive Gas-Fired Heater, ETL Listed, for use in tempering make-up air. 1500 CFM

Free shipping in continental US
We ship to Canada! Contact us

Direct Gas Fired Heated Make Up Air Unit with 15" Mixed Flow Direct Drive Fan

  • Supply Fan handles 1500 CFM @ 0.500" wc ESP, Fan runs at 1691 RPM.
  • Heater supplies 88138 BTUs. 55°F Temperature Rise. [Fuel: Natural Gas]
  • Supply Motor: 1.000 HP, 1 Phs, 115 V, 60 Hz, 11.6 FLA, TEAO-ECM (Totally Enclosed Air Over Electronically Commutated Motor)
  • Down Discharge - Air Flow Right -> Left

200/240 V, Single or Three Phase Input *available, please call for 1 phase input

Construction Features:

  • Sloped Filtered Intake for Size #1 Modular Heater.  21.813" Wide x 44.375" Long x 23.375" High.  Includes 2" MV EZ Kleen Metal Mesh Filters.
  • Gas Manifold for DF1 GM - BTU 0 - 550001 - 7 in. w.c. - 14 in. w.c., No Insurance Requirement (ANSI), BV250-66
  • Down Discharge Construction for Size 1 Direct Drive AHUs
  • Gas Pressure Gauge, 0-35", 2.5" Diameter, 1/4" Thread Size
  • Gas Pressure Gauge, -5 to +15 Inches Wc., 2.5" Diameter, 1/4" Thread Size
  • Ship Loose Gas Strainer. To be installed upstream of unit connection. 3/4" Connection
  • Motorized Back Draft Damper 16" X 18" for Size 1 Standard & Modular Heater Units w/Extended Shaft, Standard Galvanized Construction, 3/4" Rear Flange, Low Leakage, TFB120S Actuator Included
  • Unit mounted: 0-150°F Discharge Temp Control, Heating Activation Based On Intake Set Point, Manual Blower Mode. Use with MUA – remote controlled HMA’s can be ordered separately
  • ECM Wiring Package and Manual or 0-10VDC Control for Supply EC motors. MUA BOARD. **DO NOT ORDER UNDER WARRANTY.**
  • Curb CRB21X71X20INS Insulated On Fan #1 Flat Curb
  • Low Fire Start. Allows the burner circuit to energize when the modulation control is in a low fire position.
  • Full Bottom Curb Corner. Base flange corners fully welded or staked by factory.



Direct Drive Gas-Fired Heated Make Up Air Unit - 1500 CFM